UNIT II
POWER FLOW ANALYSIS
BUS CLASSIFICATION
1.Slack bus or Reference bus or Swing bus:
|V| and δ are specified. P and Q are un specified, and to be
calculated.
2.Generator bus or PV bus or Voltage controlled bus:
P and |V| are specified. Q and δ are un specified, and to be
calculated
3.Load bus or PQ bus:
P and Q are specified. |V| and δ are un specified, and to be
calculated
ITERATIVE METHOD
n
I Y V
p pq q
q1
S P jQ V *I
p p p P p
P jQ n
p p Y V
* pq q
V q1
P
The above Load flow equations are non linear and
can be solved by following iterative methods.
1.Gauss seidal method
2.Newton Raphson method
3.Fast Decoupled method
GAUSS SEIDAL METHOD
For load bus calculate |V| and δ from V k+1 equation
p
1 P jQ p1 n
V k1 p p Y V k1 Y V k
p Y (V k)* pq q pq q
pp P q1 qp1
For generator bus calculate Q from Q K+1 equation
P
p1 n
Q k1 1*Im(V k)* Y V k1 Y V k
p P pq q pq q
q1 qp
k+1
• Check Qp,cal with the limits of Qp
• If Q k+1 lies within the limits bus p remains as PV bus
p,cal
otherwise it will change to load bus
• Calculate δ for PV bus from V k+1 equation
• p
Acceleration factor α can be used for faster convergence
• Calculate change in bus-p voltage
V k1 V k1 V k
p p p
• If |ΔV |< ε, find slack bus power otherwise increase
max
the iteration count (k) S S
• Slack bus power= G L